no. |
identification component |
location |
problem |
action |
|
1 |
LPL 2026 E9314 1/2 “ x 5/8 bow shackle to BS3032 |
LTS |
wrong pin fitted |
Taken out of service |
|
2 |
LPL 4007 SEIFA-CE M20 dynamo eyebolt TOBS4278/1 |
LTS |
not located |
Taken out of service |
|
3 |
LPL 4008 SEIFA-CE M20 dynamo eyebolt TOBS4278/1 |
LTS |
not located |
when found withdraw |
|
4 |
LPL 559 TL20 polyester roundsling green 6 mtr circ |
WHT |
outer casing damaged |
withdraw from service |
|
5 |
LPL 472 Eastman manual chain hoist WHT 150kgs (small unit for
lifting ISIS slitunit) |
WHT |
safety catch missing from top hook |
Taken out of service |
|
6 |
LPL 529 Verlinde Manual chainhoist in lower basement 1000kg |
LTS |
hook bent & chain broken |
Taken out of service |
|
7 |
LPL 020 077-1059 Genie super lift SL18 |
WHT |
mast bent on top stage of 1st stage of lift(2) |
replaced by new electrical genie lift |
|
8 |
LPL 250 Rising platform |
WHT |
240V control wiring should be 48V |
Investigate how this can be implemented |
|
9 |
Skywinder lift SW117 136kgs |
WHT |
equipment needs to be stored under a cover |
equipment will be stored inside building |
|
10 |
LPL 127 29535 Kone electric wire rope hoist 1 tonne |
JKT |
no safe access to inspect sheave and pin |
None |
|
11 |
LPL 124 Kone elctr wire hoist with fixed suspension from dome
lowering through 4 sheaves |
INT |
no safe access to inspect sheave blocks |
discuss during next visit how these items can be inspected |
|
12 |
LPL825 123225 Hydraulic grating shutter interlock lifting table |
INT |
no SWL marked |
This is a dedicated trolley for A&G box and IDS. Find out total
weight off that and mark this as SWL |
|
13 |
LPL 4034 No.1 Alba hand winch C/W wire rope 500kgs |
INT |
tooth missing on ratched pawl |
locate and withdraw from service if possible |
|
14 |
LPL 4036 No.2 Alba hand winch C/W wire rope 500kgs |
INT |
tooth missing on ratched pawl |
locate and withdraw from service if possible |
|
15 |
LPL 097 EN3354 A&G lift frame 2.5mtr telescope 1 tonne |
INT |
control circuit via limit switches is 240V AC. Final wiring to
limit switches exposed and does not comply with current
legislations. Replace limit switches to enclosed cable type or
down rate control circuit to 12/24V via transformer |
Investigate how this can be implemented. I understand already
something has been looked at |
|
16 |
LPL 40073735 Matbro telescopic fork lift 2700kgs |
INT |
Flashing lamp not working, reversing lamp broken, off side
indicator lens broken, tyres badly worn |
fix defects and purchase tyres |
|
17 |
LPL 992 V8531 Open boddied turnbuckle F/T ISIS trolley LPL425
850kgs |
|
threaded end of turnbuckle is bent |
This is being addressed by replaced this kit with dedicated
slings. We wait for info from Eurolifting for quote on suitable
kit |
|
18 |
LPL 1000 C4 10mm wire rope sling F/T ISIS trolley LPL425 896kgs |
|
8 shackles are attached to each other 2 x 4 this is not good and
should be replaced by a suitable means of adjustment |
This is being addressed by replaced this kit with dedicated
slings. We wait for info from Eurolifting for quote on suitable
kit |
|
19 |
A1206 Dynafore load indicator 2 tonne |
|
No test certificate, should be calibrated every 12 months |
During next visit Eurolift will take one at a time to UK to get
certified. |